1. AC input
1) Voltage range: AC 1~300V
2) Current range: AC 20mA-100A
3) Signal processing: special metering chip is adopted, and 24 bit AD is adopted.
4) Overload capacity: 1.2 times the range is sustainable; The instantaneous (<20ms) current is 5 times, the voltage is 1.2 times, and the range is not damaged.
5) Input impedance: voltage channel >1k Ω /v.
2. Communication interface
1) Interface type: 1-way RS-485 communication interface.
2) Communication protocol: MODBUS-RTU protocol.
3) Data format: software can set "n, 8,1", "E, 8,1", "O, 8,1", "n, 8,2".
4) Communication rate: the baud rate of RS-485 communication interface can be set to 9600, 19200, 38400bps; The baud rate defaults to 9600bps.
3. Test output data
Voltage, current, power, electric energy and other electrical parameters.
4. Measurement accuracy
Voltage, current and power: ± 1.0%; Active kwh is level 1.
5. Electrical isolation
RS-485 interface is isolated from AC power supply, voltage input and current input; Isolation withstand voltage 2000vac.
6. Power supply
1) Two power supply modes are selected: take power from the input AC phase C, and note that the voltage range is ac 85~265V; DC power supply can also be selected, and the input range is +9v~24v(by default).
2) Typical power consumption: ≤ 1W.
7. Working environment
1) Working temperature: -20~+70 ℃; Storage temperature: -40~+85 ℃.
2) Relative humidity: 5~95%, no condensation (at 40 ℃).
3) Altitude: 0~3000 meters.
4) Environment: a place without explosion, corrosive gas and conductive dust, and without significant shaking, vibration and impact.
8. Temperature drift
≤100ppm/℃
9. Installation method
The distance between screw fixing and installation holes is 105*58.5mm
10. Product size
304*84mm