Wholesale Price Data Center Rack Pdu - JSY-MK-164 Control type intelligent PDU meter – JIAN SI YAN

Description:


Product Detail

Product Tags

Related Video

Feedback (2)

As for competitive prices, we believe that you will be searching far and wide for anything that can beat us. We can state with absolute certainty that for such quality at such prices we are the lowest around for Dc Charging Point , Portable Energy Meter , Bidirectional Electric Meter , We encourage you to make contact as we are looking for partners in our venture. We are sure you will find doing business with us not only fruitful but also profitable. We are ready to serve you with what you require.
Wholesale Price Data Center Rack Pdu - JSY-MK-164 Control type intelligent PDU meter – JIAN SI YAN Detail:

Technical Parameter

1. Single phase AC input
Voltage range: 100V, 220V, 380V, etc.
Current range: 5A, 50a, etc; The model of external opening current transformer is optional.
Signal processing: special metering chip is adopted, and 24 bit AD is adopted.
Overload capacity: 1.2 times the range is sustainable; The instantaneous (<20ms) current is 5 times, the voltage is 1.2 times, and the range is not damaged.
Input impedance: voltage channel >1k Ω /v.

2. Communication interface
Interface type: 1-way RS-485 communication interface.
Communication protocol: MODBUS-RTU protocol.
Data format: software can set “n, 8,1″, “E, 8,1″, “O, 8,1″, “n, 8,2″.
Communication rate: the baud rate of RS-485 communication interface can be set to 9600, 19200, 38400bps; The baud rate defaults to 9600bps.

3. Test output data
Voltage, current, power, electric energy and other electrical parameters.

4. Measurement accuracy
Voltage, current and power: ± 1.0%; Active kwh is level 1.

5. Electrical isolation
RS-485 interface is isolated from AC power supply, voltage input and current input; Isolation withstand voltage 2000vac.

6. Power supply
Power supply mode: the voltage range is ac85~265
Typical power consumption: ≤ 1W.

7. Working environment
Working temperature: -20~+70 ℃; Storage temperature: -40~+85 ℃.
Relative humidity: 5~95%, no condensation (at 40 ℃).
Altitude: 0~3000 meters.
Environment: a place without explosion, corrosive gas and conductive dust, and without significant shaking, vibration and impact.

8. Temperature drift: ≤100ppm/℃.

9. Product size: 90mm*40mm.


Product detail pictures:

Wholesale Price Data Center Rack Pdu - JSY-MK-164 Control type intelligent PDU meter – JIAN SI YAN detail pictures

Wholesale Price Data Center Rack Pdu - JSY-MK-164 Control type intelligent PDU meter – JIAN SI YAN detail pictures

Wholesale Price Data Center Rack Pdu - JSY-MK-164 Control type intelligent PDU meter – JIAN SI YAN detail pictures

Wholesale Price Data Center Rack Pdu - JSY-MK-164 Control type intelligent PDU meter – JIAN SI YAN detail pictures


Related Product Guide:

Adhering into the theory of "quality, services, efficiency and growth", now we have gained trusts and praises from domestic and international shopper for Wholesale Price Data Center Rack Pdu - JSY-MK-164 Control type intelligent PDU meter – JIAN SI YAN, The product will supply to all over the world, such as: Guyana, Bangladesh, Durban, With the goal of "zero defect". To care for the environment, and social returns, care employee social responsibility as own duty. We welcome friends from all over the world to visit and guide us so that we can achieve the win-win goal together.
  • Managers are visionary, they have the idea of "mutual benefits, continuous improvement and innovation", we have a pleasant conversation and Cooperation.
    5 Stars By Donna from Brazil - 2018.05.13 17:00
    Products and services are very good, our leader is very satisfied with this procurement, it is better than we expected,
    5 Stars By Ethan McPherson from Turkey - 2017.05.02 18:28

    RELATED PRODUCTS